 POWER QUALITY ANALYZER 3197
Power Measuring Instruments
T h e M o s t C o m p r e h e n s i ve Portable PQA on The Market
Catch Power Quality Problems on the Fly...
Monitor for: Inrush Current Voltage Swells Voltage Dips Transient Overvoltage Interruptions Measure and Record: Power and Power Factor Active/Reactive Energy Demand Load Changes (with graph display!) Voltage and Current
...Before They Catch You!
Measure Power and Power Quality on Single to Three-Phase Circuits Quickly and Effortlessly
39 17
Feature 2: QuickSet
With QuickSet, all you have to do is just Set, Clamp and Measure!
Line frequency Measurement Interval Nominal Voltage Swell Event Dip thresholds against nominal Interruption voltage Transient : : : : : : : Auto Auto Auto 110% 90% 10% ON Testing Parameters Automatically Defined by QuickSet Redefine Thresholds Easily with Intuitive Key Panel
P Q A
Feature 1: Vector Multimeter
For checking the wiring map and vectors in a single window
Use the wiring map, vector map and data monitor to c he c k for pr op e r wiring before taking measurements - don't miss out on important power data just because of minor wiring mistakes!
A quick glance at the correct vector map will show you if your wiring is correct
Let QuickSet help you take care of all the time-consuming setup procedures. All you need to do is select your circuit, clamp sensor and range, and then let QuickSet do the rest of the work for you.
Feature 3: Power & Power Quality
Measure all the necessary power parameters simultaneously
Get a crystal clear picture of the voltage fluctuation on all channels Check for sudden inrush during motor startup and diagnose breaker trips due to over current all on the same measurement interface. View RMS data for every half cycle over a 30 second period on a large graph display
All items are recorded as events so that a quick understanding can be obtained just by viewing the waveform

Power & Energy Voltage Demand Current Load Changes Frequency THD(voltage) Power Active/Reactive and Power Factor Energy Voltage Fluctuation (dips and swells)
2

Power Quality Inrush Current Voltage Swells Voltage Dips Transient Overvoltage Interruptions
Setting Up is as Easy as 1-2-3
Use QuickSet to automatically set the default values for line frequency, nominal voltage, interval, and power quality thresholds for event detection
1
Select your wiring
2
Select your clamp sensor
Use the correct vector diagram to check that your wiring is right before measuring, particularly useful when measuring 3-Phase circuits
WIRIN G
3
RE C&
QuickSet
Toggle between screens to customize your measurement settings
Make detailed settings on how and when to measure, and customize your level of event detection as desired.
EVE NT
RE SU A ME
Obtain real-time moving data on voltage, current, power, and more!
Select from 5 Types of Color-coded Input Terminal Labels to Suit Your Application Region
Type 1 2 3 4 5 N Black Blue Black Blue White U1 Red Orange Yellow Black Black U2 Yellow Black Green Red Red U3 Blue Gray Red White Blue Region Japan, U.K. EU (new) China EU (former) N. America
Monitor Trends while Recording
WAVEFORM
Toggle between screens using VIEW key for instantaneous power data
lPull Strap Through for Ultimate Portability lAC Adapter for Quick Recharge or Long Recordings lUSB Port for PC Compatibility lPower Switch
One-touch switching between graph and numerical data
RMS, Phase Angle and Lead and Lag Full-color waveforms and RMS readings
lConvenient Stand for Hands-free Viewing
VECTOR
lRugged and Durable Casing to withstand even the toughest environments and uses
3
Record and Inspect
(even while measuring)
Find the max, min and average values for any point using the cursor function
Auto-Data Compression Lets You Record for up to 125 Days
DIP/SWELL
RMS
Toggle between the trend graphs for a complete analysis of the power situation
Consumed & Regenerated Active Power Lag and Lead of Reactive Power
Get a detailed picture during voltage anomalies fluctuation range for all 3 channels are displayed
ENERGY
Demand Graph and maximum and average values displayed in one window
DEMAND
Display events AND their waveforms at the same time
DMM
Harmonic waveforms of voltage, current and active power to the 50th order
Identify Power Quality Problems
Inrush current fluctuations are captured in RMS at a fast 10ms sampling rate and displayed across a 30-second window
WAVEFORM
Switch between voltage and current graphs, and zoom in on the time axis at the touch of a button
Toggle between events for a complete picture of the power anomaly Store up to
50 Events
DETAIL
"I" marks an Inrush Event RMS voltage fluctuations such as swells and dips are clearly displayed at event detection
HARMONICS
GRAP/LIST
INRUSH
Record up to 20 graphs in internal memory
Scroll down and select to display the finer details of any event
RMS
4
Feature 4: Bundled PC Application Software
Two Integrated Programs for Data Download and Viewing
St andard USB conne c tion let s you download dat a at a snap, and immediately view your measurements with the DataViewer
Mobility, Portability Plus Convenient Data Transfer Right to Your PC
Feature 5: Compact Design Makes for Long Battery Life
6 Hours of Continuous Use on a Single Recharge
Non-volatile Ni-MH rechargeable battery pack keeps important measurement data in memory even after power is turned off.
Connect to multiple 3197 units simultaneously using a USB hub Open downloaded recordings with DataViewer to manage and process your captured power data on your PC. Event List
A PQA that TRULY fits in the palm of your hand.
Standard 3197 Package Fulfills All the Requirements for Checking Voltage Anomalies
Time Plot Graph
Voltage Cords
AC Adapter
USB Cable Carrying Case
Event Details
Event Waveform Settings
Rechargeable Battery Pack
PC Application
To measure current and power, please select one or more of our HIOKI Clamp On Sensors detailed on the back of this catalog.
< Measurement Specifications (Guaranteeed Accuracy Period: 1 Year)
RMS Voltage and Current Voltage Accuracy Current Accuracy Voltage (1/2) RMS Measurement Accuracy Current (1/2) RMS Measurement Accuracy Frequency Accuracy Active Power Accuracy (for consumption and regeneration) True RMS (200 ms calculation ) 0.3% rdg. 0.2%f.s 0.3% rdg. 0.2%f.s. + Clamp sensor accuracy True RMS (one cycle calculation refreshed every half cycle) 0.3% rdg. 0.2%f.s. True RMS (half-cycle calculation, half-cycle voltage synchronized) 0.3% rdg. 0.2%f.s. + Clamp sensor accuracy Effective Measurement range: 45.00 to 66.00 Hz 0.01 Hz 1 dgt. (when input is at least 10% of range) 0.3% rdg. 0.2% f.s. + clamp-on sensor accuracy (P.F.=1)
< Event Detection
Voltage Swells (Rise), Voltage Dips (Drop), Interruptions Inrush Current Transient Overvoltage Timer Detection Manual Detection Thresholds Event Recording Lengths Waveform Event voltage fluctuation graph Inrush current graph Maximum Number of Recordable Events RMS value detected using voltage (1/2) measured every half cycle RMS value detected using current (1/2) every half cycle Detection Range: 50 Vrms (70.7 Vpeak equiv.) or more, 10 to 100 kHz Detect events at preset intervals selectable from OFF, 1, 5, 15 or 30 minutes; 1, 2 or 12 hours; or 1 day Detect events when keys are pressed Set to OFF or to specified value, except for detection of transient overvoltages. (Waveform recording not available for transients.) 20ms before detection + 200ms upon detection + 20ms after detection 0.5s before + 2.5s after detection 0.5s before + 29.5s after detection 50 event waveforms, 20 event voltage fluctuation graphs, 1 inrush current graph, 1000 event counts
Reactive Power Accuracy 1 dgt. of calculation from each measurement value (for lags and leads)
Effect of Power Factor Apparent Power Accuracy Power Factor and Displacement Power Factor Accuracy (leading phase indicated) Active or Reactive Energy Consumption Accuracy
Demand
1.0% rdg. (50 /60Hz, P.F.=0.5) 1 dgt. of calculation from each measurement value 1 dgt. of calculation from each measurement value (DPF calculated from phase difference between fundamental voltage and current waveforms) Selectable between consumption, regeneration, lag and lead 1 dgt. applied to active and reactive power measurement accuracy Selectable between active or reactive power 1 dgt. applied to active and reactive power measurement accuracy Up to 50th (2048 points/window, rectangular) 1st to 15th order 0.5% rdg. 0.2% f.s. 16th to 25th order 1.0% rdg. 0.3% f.s. 26th to 35th order 2.0% rdg. 0.3% f.s. 36th to 45th order 3.0% rdg. 0.3% f.s. 46th to 50th order 4.0% rdg. 0.3% f.s. (add accuracy of clamp sensor to harmonic current accuracy) Peak Voltage and Current, K Factor, Voltage Unbalance Factor, Max/Min/Ave of Time Series
< Input Specifications
Single-phase 2-wire (1P2W), single-phase 3-wire (1P3W), three-phase 3-wire (3P3W2M and 3P3W3M), three-phase four-wire (3P4W and 3P4W2.5E) Measurement Line frequency Auto-select (50/60 Hz) Maximum Allowable Input Voltage input terminal: 780 V AC (1103 Vpeak) Voltage Current input terminal: 1.7 V AC (2.4 Vpeak) Voltage input terminal: CATIII 600 V AC, CATIV 300 V AC (50/60 Hz) Maximum Rated Voltage Current input terminal: per clamp-on sensors used to Ground Simultaneous digital sampling of voltage and current Measurement Method (sampling frequency: 10.24 kHz per channel) Wiring Configurations Voltage Measurement Range 600.0V (Crest factor 2 or less) Current Measurement Range: Manual ranging according to clamp sensor (Crest factor 3 or less) Clamp Sensor Range Clamp Sensor Range 9657-10, 9675 500.0 mA/5.000 A 9661, 9667 (500A) 50.00 A/500.0 A 9694, 9695-02 5.000 A/50.000 A 9669 100.0 A/1.000 kA 9660, 9695-03 10.00 A/100.0 A 9667 (5000A) 500.0 A/5.000 kA
Accuracy
Harmonic Analysis Orders
Harmonic Voltage, Current and Power Accuracy (accuracy is not defined for harmonic power)
Other Measurement Items
500mA 300.0W/600.0W/900.0W 100A 60.00kW/120.0kW/180.0kW Power Measurement 5A 3.000kW/6.000kW/9.000kW 500A 300.0kW/600.0kW/900.0kW Range: Depends on combination of current range 10A 6.000kW/12.00kW/18.00kW 1kA 600.0kW/1.200MW/1.800MW and measurement line 50A 30.00kW/60.00kW/90.00kW 5kA 3.000MW/6.000MW/9.000MW
5
< BASIC SPECIFICATIONS
Display Display languages Display refresh rate Clock functions Real-Time Clock accuracy Internal Memory Capacity Maximum recording time Interval Settings Demand period Recordable Items 4.7-inch color STN LCD English, Japanese or Chinese (Simplified) Approx. once per second Auto calendar, auto leap year, 24-hour format Within 13 seconds/month 4MB 125 Days AUTO, 1, 5, 15 and 30 min., and 1 hour (AUTO sequentially selects 1, 2, 10, 30 seconds, 1, 5, 15 and 30 min., and 1 hour automatically) 15 min., 30 min. and 1 hour All parameters (incl. max/min/average values)
< ENVIRONMENTAL AND SAFETY-RELATED SPECIFICATIONS
Operating environment Temperature and humidity Applicable standards Indoors, up to 2000 m (6562-ft.) ASL Storage -10 to 50C (14 to 122F), 80% RH or less (non-condensating) Operation 0 to 40C (32 to 104F), 80% RH or less (non-condensating) EN61010-1: 2001, Pollution degree 2, Safety Measurement Categories III (600 V) and IV (300 V) (anticipated transient overvoltage 6000 V) EN61326:1997 + A1:1998 + A2:2001 + A3:2003 Class EMC A; EN61000-3-2:2000, EN61000-3-3:1995 + A1:2001 Model 9418-15 AC Adapter or Model 9459 Battery Pack (Maximum rated power: 23 VA (with AC adapter)
Power source
< INTERFACE SPECIFICATIONS
Interface Connection destination USB 2.0 (Full Speed) Computer operating on Windows 2000/XP
Continuous Approx. 6 hours operating time (after full charge, with 5 min. auto-off LCD backlight) with battery pack 128 W x 246 H x 63 D mm (5.04"W x 9.69"H x 2.48"D) Dimensions and (including stand) mass Approx. 1.2 kg (42.3 oz.) (with battery pack)
< CLAMP ON SENSOR SPECIFICATIONS
9694
3m cord
9660
3m cord
9661
3m cord
9669
3m cord
9667
CAT III 1000V
9695-02
9695-03
MODEL
CAT III 300V Measurable conductor diameter CAT III 300V 15mm CAT III 600V 46mm CAT III 600V 55mm, 80x20mm
2m from sensor to circuit 1m from circuit to connector
CAT III 300V
CAT III 300V 15mm
254mm
Primary current rating Output voltage
Accuracy
AC 5A AC 10mV/A
AC 100A AC 1mV/A
AC 500A AC 1mV/A
AC 1000A AC 0.5mV/A
AC 500A/5000A AC 500mVf.s.
AC 50A AC 10mV/A
AC 100A AC 1mV/A
Amplitude 0.3%rdg.0.02%f.s. 0.3%rdg.0.02%f.s. 0.3%rdg.0.01%f.s. 1.0%rdg.0.01%f.s. 2.0%rdg.1.5mV 0.3%rdg.0.02%f.s. 0.3%rdg.0.02%f.s. (45 to 66 Hz) Phase within 1 within 2 within 1 within 0.5 within 1 within 2 within 1 (5Hz to 5kHz) (minimum 10% input)
Frequency characteristic (accuracy deviation) Max. rated voltage to earth(insulated conductor)
within 1.0% at 40Hz to 5kHz (9669: within 2.0%) 300Vrms 300Vrms 130A continuous 600Vrms 550A continuous 600Vrms
3dB at 10Hz to 20kHz 1000Vrms
within 1.0% at 40Hz to 5kHz 300Vrms 60A continuous 130A continuous
Maximum allowable 50A continuous input (45 to 66 Hz) Dimensions and weight 46Wx135Hx21Dmm, 230g Requirements
1000A continuous 10000A continuous
46Wx135Hx21Dmm, 230g
77Wx151Hx42Dmm, 360g
100Wx188Hx42Dmm, 590g Sensor length 910mm, 140g
9445-02/03 AC Adapter (Option)
51Wx58Hx19Dmm, 50g
9219 Connection Cord (3m; Option)
< COMPLETE LIST OF OPTIONS
9660 9661 9667 9669 9694 9695-02 9695-03 9219 9657-10 9675 9438-05 9418-15 9459 9624-50 CLAMP ON SENSOR (100A) CLAMP ON SENSOR (500A) FLEXIBLE CLAMP ON SENSOR (5000A) CLAMP ON SENSOR (1000A) CLAMP ON SENSOR (5A) CLAMP ON SENSOR (50A) CLAMP ON SENSOR (100A) CONNECTION CORD (for the 9695-02/9695-03) CLAMP ON SENSOR (10A) CLAMP ON SENSOR (10A) VOLTAGE CORD (bundled with the standard 3197) AC ADAPTER (bundled with the standard 3197) BATTERY PACK (bundled with the standard 3197) PQA-HiVIEW Pro PC Application Software (available Fall 2006)
MODEL
9675
3m cord
9657-10
3m cord
CAT III 300V Measurable conductor diameter
CAT III 300V
30mm AC 10A AC 100mV/A 1.0%rdg.0.005%f.s. within 5
40mm AC 10A AC 100mV/A 1.0%rdg.0.05%f.s. within 3
Primary current rating Output voltage Amplitude Accuracy (45 to 66 Hz)
Phase Accuracy (50/60Hz) Residual Current
1mA (10A on forward and return) 5mA (100A on forward and return)
Frequency characteristic within 5% at 40Hz to 5kHz within 3% at 40Hz to 5kHz (accuracy deviation) Max. rated voltage to earth Maximum allowable input
300Vrms (insulated conductor) 10A continuous 30A continuous
<3197 STANDARD BUNDLE CONFIGURATION
Includes all the equipment you need to measure voltage. For current or power measurements, please select from our wide assortment of clamp on sensors.
Dimensions and weight 60Wx113Hx24Dmm, 160g 74Wx145Hx42Dmm, 380g Notes
Not compatible with power measurements
3P4W Circuit testing of motors and breakers: 3197 Standard Package + 9661 (500A Sensor)x3 3P4W Circuit testing of external CTs: 3197 Standard Package + 9694 (5A Sensor)x3 3P Leakage testing: 3197 Standard Package + 9675 (10A Sensor)x3
DISTRIBUTED BY
9438-05 VOLTAGE CORD (3m cord length), 9459 BATTERY PACK, 9418-15 AC ADAPTER, USB Cable, Input Terminal Labels, Input Cord Labels, 3197 Applications PC Program (CD-ROM), strap, carrying case, measurement guide, instruction manual
HEAD OFFICE : 81 Koizumi, Ueda, Nagano, 386-1192, Japan TEL +81-268-28-0562 / FAX +81-268-28-0568 E-mail: os-com@hioki.co.jp HIOKI USA CORPORATION : 6 Corporate Drive, Cranbury, NJ 08512 USA TEL +1-609-409-9109 / FAX +1-609-409-9108 E-mail: hioki@hiokiusa.com
Shanghai Representative Office : 1310 Shanghai Times Square Office 93 Huaihai Zhong Road Shanghai, 200021, P.R.China TEL +86-21-6391-0090, 0092 FAX +86-21-6391-0360 E-mail: info@hioki.cn
All information correct as of May. 31, 2006. All specifications are subject to change without notice.
3197E1-65E-10K
Printed in Japan


▲Up To Search▲   

 
Price & Availability of 3197

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X